20306760 12/14 Rev. 1 SDDVT Series Stardance® Direct Vent Gas HeaterInstallation and Operating InstructionsModels: SDDVT(CS)CBSB, SDDVT(CS)BSSB, SDD
When planning the installation, consider the location of the vent terminal and clearances. Some of the most common clearances to keep in mind are show
General Venting Information - Termination LocationV XX X D E B B B C B M B AJ K F L VENT TERMINATION AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PER
Figure 12 Termination clearances.Venting Requirements - Natural Vent OnlyFP567NVBR/NVBC VENTING RUNS11/12/97Venting Runs Horizontal Run (in feet)Vert
Venting Requirements and Options - Direct Vent ONLYApproved Vent System ComponentsThe Stardance Heater must be vented to the outdoors through an adjac
Vermont Castings Group Vent ComponentsThe following kits are available to meet the needs of most installations. All pipe has a 7” outer diameter and i
Install the Optional Fan - SDDVT SeriesIf you are installing the optional convection Fan Kit #2767 (FK26), continue here. If you are not installing a
Venting System Assemlby - Direct VentGeneral InformationThe Stardance is approved for installation only with the vent components listed on Pages 13 &a
ST355bdura ventattach inner assyno restrictor plate6/07 djtCEMENT1/4-20 x 3/8 Phillips ScrewsInner Adapter PipeST355b Figure 21 DuraVent - install i
5. Install rst the inner then the outer straight pipe sec-tion(s), trimmed end down, to the point of the elbow. Drill 3 holes through each joint and
ST218install snorkel12/6/99 djt4”Waterproof Seal Around PIpeFirestopWall Screws and AnchorsSnorkel Termination CapDrainWindow WellST218aFigure 29 S
Installation & Operating InstructionsGeneral Information ...3Requirements for Massachusetts
ST222vent thru ceiling12/99#7DVAIS Attic Insulation Shield#7DVFS Firestop in Upper Floor#7DVFSFirestop in CeilingUse Four 8dNailsST222Figure 31 Insta
Vent Termination (VC)Storm Collar (SC)Roof Flashing (AF)Ceiling Support (CS)Trim Plate (TP)Pipe LengthPipe LengthAppliance Adapter (AAV)ST924Vertical
Supporting DIRECT-TEMP: Vertical SupportVertical installations can be supported by two methods:Ceiling Support (CS) (used in at ceiling installation)
interference with wall studs, electrical wiring, conduit, plumbing pipe or other obstructions. The termination should be located at least 12” (305 mm)
ST931Selkirk Horiz termination6/07Horizontal TerminationFigure 41 Horizontal termination.ST932Selkirk standoff6/07Vinyl Siding StandoffST932Horizonta
(610 mm)] either the cathedral ceiling support box or the ceiling support plate and assemble lengths of pipe to sat-isfy this distance. Do not attach
2. Install the rear log by mating the notch on the bottom of the log with the raised notch on the back left side of the ember bed. (Figure 47) Ensure
LG495SDDVT logs complete6/07Rear LogTop LogLeft LogRight LogEmber BedFigure 493. Install the left log by mating the hole on the bottom of the log wit
To connect Natural Gas, use a tting with 3/8” NPT nipple on the valve side and 1/2” natural gas supply line with an input of 28,000 BTUs at a manifol
Install the Front PlateHold the front plate by the window bars and lift it into posi-tion, engaging the two steel tabs on the top corners behind the a
General InformationThe Stardance Direct Vent/Natural Vent Room Heater, Model Nos. SDDVTCB, SDDVTEB, SDDVTBS, SDDVTBD, SDDVTBM, SDDVTCSCB, SDDVTCSEB,
The Stardance is operated with the front plate in place with the doors open or closed. The barrier screen is designed to attach over the doors, or ove
3. Open control access panel.4. Push in gas control knob slightly and turn clockwise to “OFF”. Do not force.5. Close control access panel.1. STO
Troubleshooting the Gas Control System (SDDVT Series)NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “O
Instructions for RCSITEASDDVTCS SeriesCAUTION: The RCSITEA is only certied for use on vent-ed heater rated equipment.This remote control system provi
Initial StartupFigure 611. After initial power up or when RESET button is pressed, the transmitter is reset. The reset button is located behind the ba
Transmitter Thermal ShutdownFigure 691. If transmitter measures a room temperature exceed-ing 99° F, the LCD will display "HI" and the trans
Testing Remote Control System1. Light the gas appliance following the lighting instruc-tions on Page xx. Conrm the pilot light is on; it must be in
Fuel Conversion InstructionsWARNING! This conversion kit shall be installed by a qualied service agency in accordance with the manufact
SDDVTCS Series Models1. Using the TORX T20 bit remove and discard the three (3) pressure regulator mounting screws from the old pressure regulator as
ST919tilt ember bed6/07Pem StudsST919Figure 83 Tilt ember bed slightly to correctly place on venturi and air shutter.Orice BracketVenturi BracketCO14
Installation RequirementsRequirements for the Commonwealth of MassachusettsAll gas tting and installation of this heater shall only be done by a
MaintenanceYour Stardance Gas Heater will provide years of service with minimal upkeep. The following procedures will help ensure that your stove cont
Figure 84 Remove the stove front and glass frame.Gasket ReplacementThe Stardance Gas Heater uses a ‘tadpole’ type gasket to seal between the glass pa
OFFONThermostat(Optional)ThermopileBlackBlackMillivoltGas ValveSt124bon/off/switchwiring1/11/00 djtTP/THTPTHWiring Diagrams - SDDVTST124bOn/Of
T HT P / T H 120V AC AdaptermV ValveBlackBlackSIT HI / LOValveFemaleMaleST1090SIT valve wiring120V AC Plug120V ACBlowerReceiverFigure 90 SIT Hi/Lo bl
Vermont Castings Group reserves the right to make changes in design, materials, specications, prices and discontinue colors and products at any time,
Replacement PartsRef. Description SDDVT/SDDVTCS1. Log Set - Complete 200125511a. Log Rear 200125461b. Log Right 200125481c. Log Left 200125471d. Lo
*Use common super glue or silicone to attach magnets.Color Top Left End Right End Front OP Left Door*Right Door*Left Door**Right Door**Classic Black
Optional AccessoriesFan Kit - STDDVTFK26 FanThe FK26 fan helps distribute heated air from within the rebox out into the room. The fan is controlled
LIMITED LIFETIME WARRANTY Vermont Castings Group warrants that all cast iron parts, the combustion chamber, ceramic burner, and heat exchanger of eve
This page intentionally left blank.49Stardance® Direct Vent/Natural Vent Gas Heater20306760
Stardance Direct Vent / Natural Vent Dimensions26³⁄₄"(680 mm)25¹⁄₂"(648 mm)14¹⁄₂"(355 mm)3"(76 mm)CL12734Stardance dim8/07 djtSu
This page intentionally left blank.50Stardance® Direct Vent/Natural Vent Gas Heater20306760
This page intentionally left blank.
149 Cleveland Drive • Paris, Kentucky 40361www.vermontcastingsgroup.comEFFICIENCY RATINGSMODELENERGUIDE RATINGS FIREPLACE EFFICIENCY PERCENTAGED.O.E
Clearance RequirementsMinimum Clearances to Combustible MaterialsMeasure side clearances as shown in Figures 3 and 4 from the outer edge of the cast i
ST128bStardanceflue centerline9/28/00 djtCLCLBDCAParallel Installation: Minimum Clearance and Flue Centerline, Direct Vent and Natural VentST128bSto
Weight: Fully assembled; 202 lbs.Gas Inlet and Manifold Pressures Natural LP (Propane) Inlet Minimum 5.5” w.c. 11.0” w.c. Inlet Maximum 14.0”
Vertical Termination - Direct Vent ONLYA vertical vent system must terminate no less than 8’ (2.44 m) and no more than 40’ (12 m) above the appli-ance